EasyManua.ls Logo

Siemens Simatic S7-1500R - Product Overview; Rear View of the CPU

Siemens Simatic S7-1500R
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cyclic program execution
3.1 Cycle
Cycle and response times
Function Manual, 10/2018, A5E03461504-AD
23
Cycle control point
When the cycle control point is reached, the CPU has completed the cycle program and is
no longer executing OBs. All user data are consistent at this time. Requirement is that no
communication that modifies user data (such as HMI communication or PUT/GET
communication) is active.
The cycle control point marks:
The end of a cycle and its cycle time statistics
The start of the next cycle and its cycle time statistics
The restart of the monitoring of the configured maximum cycle time
(time-out counter is reset)
The cycle control point is reached depending on which of the following events occurred last:
End of the last cyclic OB
Expiry of the minimum cycle time (if configured)
After the cycle control point has been reached, the CPU executes the following steps:
1. Writes the process image outputs to the output modules
2. Reads the state of the inputs into the input modules
3. Executes the first cyclic OB

Other manuals for Siemens Simatic S7-1500R

Related product manuals