Cyclic program execution
3.2 Cycle time
Cycle and response times
34 Function Manual, 10/2018, A5E03461504-AD
ET 200pro
1516pro(F)-2 PN
Hardware interrupt
80 μs
Time-of-day interrupt
80 μs
Time-delay interrupt 80 μs
Cyclic interrupt
80 μs
Table 3- 4 Basic time expenditure for an error OB
S7-1500
1511(F)-1 PN
1511T(F)-1 PN
1511C-1 PN
1512C-1 PN
1513(F)-1 PN
1515(F)-2 PN
1515T(F)-2 PN
1516(F)-3 PN/DP
1516T(F)-3 PN/DP
1517(F)-3 PN/DP
1517T(F)-3 PN/DP
1518(F)-4 PN/DP
1518(F)-4 PN/DP MFP
Programming
error
90 μs 80 μs 20 μs 12 μs
I/O access error
90 μs
80 μs
20 μs
12 μs
Time error
90 μs
80 μs
20 μs
12 μs
Diagnostic inter-
rupt
90 μs 80 μs 20 μs 12 μs
Module fail-
ure/recovery
90 μs 80 μs 20 μs 12 μs
Station fail-
ure/recovery
90 μs 80 μs 20 μs 12 μs
S7-1500R/H* in RUN-Solo system state
1513R-1 PN
1515R-2 PN
1517H-3 PN
Programming
error
170 μs 140 μs 20 μs
I/O access error
170 μs
140 μs
20 μs
Time error
170 μs
140 μs
20 μs
Diagnostic inter-
rupt
170 μs 140 μs 20 μs
Module fail-
ure/recovery
170 μs 140 μs 20 μs
Station fail-
ure/recovery
170 μs 140 μs 20 μs
* Additional information about cycle and response times of R/H CPUs is available in the section "Cycle and response times