EasyManua.ls Logo

Siemens Simatic S7-1500R - Technical Specifications; Status;Control; Forcing; Diagnostic Buffer

Siemens Simatic S7-1500R
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cyclic program execution
3.4 Response time for cyclic and time-driven program execution
Cycle and response times
44 Function Manual, 10/2018, A5E03461504-AD
Update time of the backplane bus for ET 200SP CPUs
The following table shows the central (typical) update times of the backplane bus for the
ET 200SP CPUs.
Table 3- 6 Update time of the ET 200SP CPUs
Update time of the CPU
ET 200SP
1510SP(F)-1 PN
1512SP(F)-1 PN
1515SP(F)-PC
Update time for
central I/O
250 μs to 1 ms, depending on number and type of central I/O modules
1
1
The duration of the update time depends on the number of the I/O modules and their type (ST, HF, HS). The update
time is set at 1 ms for a max. central I/O configuration with standard I/O modules. You can reduce the update time down
to 250 μs, for example, by using HF I/O modules and by reducing the number of modules.
The table below is an orientation guide. It shows the approximate relationship between the
number of ET 200SP I/O modules and the bus cycle that is used. As an example, 8 bytes of
I/O data per I/O module are assumed in the table.
Number of ET 200SP I/O modules
Input data (bytes)
Output data (bytes)
Used bus cycle (μs)
8
64
64
250
16
128
128
250
24
192
192
281.25
32
256
256
312.5
40
320
320
343.75
48
384
384
375
56
448
448
406.25
64
512
512
437.5
For I/O modules with more than 32 bytes of I/O data, the bus cycle is calculated with an I/O
module of 32 bytes. In this case the I/O module requires multiple bus cycles to update its I/O
data.

Other manuals for Siemens Simatic S7-1500R

Related product manuals