The basics of counting, measurement and position detection
2.4 Basics of counting (digital input modules)
Counting, measurement and position detection
88 Function Manual, 12/2017, A5E32009889-AG
Setting between comparison value and low counter limit
The respective STS_DQ feedback bit is set to 1 when:
Low counter limit <= counter value <= comparison value
Setting between comparison value 0 and comparison value 1
The respective STS_DQ feedback bit is set to 1 when:
Comparison value 0 <= counter value <= comparison value 1