Faults / Alarms 02.00
10-20 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Fault Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
Fault value: r047 Index 002 to 016:
1 Connection to EEPROM is faulty
Possible fault causes
A7001 electronics board is defective
A7009 backplane wiring assembly is defective
Plug-in connection X109 is defective
2 Parameter value is outside permissible value range
Possible fault causes
“Restore to default value” has never been executed
with this software (e.g. after software replacement)
A7009 backplane wiring assembly is defective
Possible remedy:
Acknowledge fault, execute “Restore to default value”
and start up the drive again
i002 Number of faulty parameter
i003 Index of faulty parameter
i004 Faulty parameter value
3 Parameter value cannot be stored on EEPROM
Possible fault causes
A7001 electronics board is defective
A7009 backplane wiring assembly is defective
Plug-in connection X109 is defective
i002 Address of fault memory location
i003 Faulty value in EEPROM
i004 Correct parameter value
11 Checksum of non-volatile data (part 1)
is not correct
12 Checksum of non-volatile data (part 2)
is not correct
13 Checksum of non-volatile data (part 3)
is not correct
20 Checksum of configuring table of parameter values is not
correct
Possible fault causes
Defective EEPROM
“Restore to default value” has never been executed
with this software (e.g. after software replacement)
Possible remedy:
Acknowledge fault, execute “Restore to default value”
and start up the drive again! Check interference
suppression measures and improve if necessary.
i002 Calculate checksum
i003 Checksum found in EEPROM
F063 Errors in compensation data of analog inputs and outputs
(active in all operating states)
This function monitors whether the factory-set compensation data for the analog inputs and outputs are plausible
Possible fault cause:
Defective A7001 or A7006 electronics board
Fault value: r047 Index 002 to 016:
11 Incorrect number of words in compensation values
for analog inputs and outputs of A7001
i002 Incorrect number of words
12 Checksum error in compensation values for
analog inputs and outputs of A7001
i002 Calculated checksum
i003 Errored checksum
13 Incorrect value among compensation values for
analog inputs and outputs of A7001
i002 Incorrect value
23 Incorrect value among compensation values for
analog inputs and outputs of A7006
i002 Incorrect value