Parameter list 02.00
11-8 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
r022 Display of torque setpoint before torque limitation
Steps: 1
=
0.1% of rated motor torque (=rated motor armature current
(P100) * magnetic flux at rated motor field current (P102))
-400.0 to 400.0
[%]
0.1% (see column
on left)
Ind: None
Type: I2
P052 = 3
r023 Display of speed controller setpoint/actual value deviation
-200.00 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r024 Display of actual speed value from pulse encoder
-200.00 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r025 Display of actual speed controller value
-200.0 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r026 Display of speed controller setpoint
-200.0 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r027 Display of ramp-function generator output
-200.00 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r028 Display of ramp-function generator input
-200.00 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r029 Display of main setpoint before limitation
-200.00 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r034 Display of firing angle (field)
0.00 to 180.00
[degrees]
0.01degrees
Ind: None
Type: O2
P052 = 3
r035 Display of field current controller actual value
0.0 to 199.9
[% of P102]
0.1% of P102
Ind: None
Type: O2
P052 = 3
r036 Display of field current controller setpoint
0.0 to 199.9
[% of P102]
0.1% of P102
Ind: None
Type: O2
P052 = 3
r037 Display of actual EMF value
-1500.0 to 1500.0
[V]
0.1V
Ind: None
Type: I2
P052 = 3
r038 Display of actual armature voltage value
-1500.0 to 1500.0
[V]
0.1V
Ind: None
Type: I2
P052 = 3
r039 Display of EMF setpoint
This parameter displays the EMF setpoint which is applied as the control
quantity in the field-weakening range.
This value is calculated from:
U
motor
rated
I
motor
rated
*
R
A
(=
P101
P100
*
P110
)
0.0 to 1500.0
[V]
0.1V
Ind: None
Type: O2
P052 = 3