02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-9
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
r040 Display of limitations:
Representation on operator panel (PMU):
3210
4
5
6
7
89101112131415
Segment alight: Corresponding limitation is reached
Segment dark: Corresponding limitation is not reached
Segment or bit
0 α
W
limit (field) reached (P251)
1 Negative current limit (field) reached (K0274)
2 α
W
limit (armature) reached (α
W
acc. to P151
for continuous current, 165° for discontinuous current)
3 ........ Negative current limit (armature) reached (K0132)
4 ........ Negative maximum speed reached (P513)
Speed limiting controller responds (B0201)
5 ........ Negative torque limit reached (B0203)
6 ........ Neg. limitation at ramp generator output reached (K0182)
7 ........ Neg. limitation at ramp generator input reached (K0197)
8 ........ α
G
limit (field) reached (P250)
9 ........ Positive current limit (field) reached (K0273)
10 ........ α
G
limit (armature) reached (P150)
11 ........ Positive current limit (armature) reached (K0131)
12 ........ Positive maximum speed reached (P512)
Speed limiting controller responds (B0201)
13 ........ Positive torque limit reached (B0202)
14 ........ Pos. limitation at ramp generator output reached (K0181)
15 ........ Pos. limitation at ramp generator input reached(K0196)
Ind: None
Type: V2
P052 = 3
Connector and binector displays
r041 High-resolution connector display:
i001: Display of connector selected in P042.01
i002: Display of connector selected in P042.02
The display value is filtered with a time constant of 300ms (see Section 8,
Sheet G120)
-200.00 to 199.99
[%]
0.01%
Ind: 2
Type: I2
P052 = 3
P042
*
High-resolution connector display:
i001: Selection of connector to be displayed in r041.01
i002: Selection of connector to be displayed in r041.02
The display value is filtered with a time constant of 300ms (see Section 8,
Sheet G120)
All connector
numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Online
r043 Connector display:
i001: Display of connector selected in P044.01
i002: Display of connector selected in P044.02
i003: Display of connector selected in P044.03
i004: Display of connector selected in P044.04
i005: Display of connector selected in P044.05
i006: Display of connector selected in P044.06
i007: Display of connector selected in P044.07
-200.0 to 199.9
[%]
0.1%
Ind: 7
Type: I2
P052 = 3
P044
*
Connector display:
i001: Selection of connector displayed in r043.01
i002: Selection of connector displayed in r043.02
i003: Selection of connector displayed in r043.03
i004: Selection of connector displayed in r043.04
i005: Selection of connector displayed in r043.05
i006: Selection of connector displayed in r043.06
i007: Selection of connector displayed in r043.07
All connector
numbers
1
Ind: 7
FS=0
Type: L2
P052 = 3
P051 = 40
Online
r045 Binector display:
i001: Display of binector selected in P046.01
i002: Display of binector selected in P046.02
i003: Display of binector selected in P046.03
i004: Display of binector selected in P046.04
0 to 1 Ind: 4
Type: O2
P052 = 3