Parameter list 02.00
11-30 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
Setting values for speed controller
P223
*
FDS
Control word for speed controller precontrol
0 Speed controller precontrol disabled
1 Speed controller precontrol acts as torque setpoint (is added to
n controller output)
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P224
*
FDS
Control word for speed controller I component
0 Set controller I component to 0 (i.e. to achieve a pure P
controller)
1 Controller I component is active
The I component is stopped when a torque or current limit is
reached
2 Controller I component is active
The I component is stopped when a torque limit is reached
3 Controller I component is active
The I component is stopped only when ±199.99% is reached
0 to 3
1
Ind: 4
FS=1
Type: O2
P052 = 3
P051 = 40
Offline
P225
FDS
Speed controller P gain
See also setting values for "Speed controller adaptation" function (P550 to
P559).
This parameter is set automatically during the speed controller optimization
run (P051=26).
0.10 to 200.00
0.01
Ind: 4
FS=3.00
Type: O2
P052 = 3
P051 = 40
Online
P226
FDS
Speed controller reset time
This parameter is set automatically during the speed controller optimization
run (P051=26).
0.010 to 10.000
[s]
0.001s
Ind: 4
FS=0,650
Type: O2
P052 = 3
P051 = 40
Online
Speed controller droop
Function: A parameterizable feedback loop can be connected in parallel to the I and P components of the speed controller (acts on
summation point of setpoint and actual value).
P227
FDS
Speed controller droop
A 10% speed droop setting causes a 10% deviation in the speed from the
setpoint at a 100% controller output (100% torque or armature current
setpoint) ("softening" of closed-loop control).
See also P562, P563, P630 and P684
0.0 to 10.0
[%]
0.1%
Ind: 4
FS=0.0
Type: O2
P052 = 3
P051 = 40
Online
P228
FDS
Filter time for speed setpoint
Filtering of setpoint by means of a PT1 element.
This parameter is automatically set to the same value as the speed
controller reset time during the speed controller optimization run (P051=26).
It may be useful to parameterize lower values when the ramp-function
generator is in use.
0 to 10000
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P229
*
FDS
Control of I component tracking for slave drive
0 On a slave drive, the I component of the speed controller is
made to follow such that M(set, ncontr.) = M(set, limit),
the speed setpoint is set to the actual speed value
1 Tracking deactivated
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P234
*
FDS
Set speed controller P component to zero
0 Set controller P component to zero (i.e. to obtain a pure I
controller)
1 Controller P component is active
0 to 1
1
Ind: 4
FS=1
Type: O2
P052 = 3
P051 = 40
Offline
11.12 Closed-loop field current control, field gating unit
P250
FDS
Alpha G limit (field)
Rectifier stability limit for firing angle of field converter
0 to 180
[degrees]
1 degree
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P251
FDS
Alpha W limit (field)
Inverter stability limit for firing angle of field converter
0 to 180
[degrees]
1 degree
Ind: 4
FS=180
Type: O2
P052 = 3
P051 = 40
Online