02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-57
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P644
*
FDS
Source for main setpoint
Selection of connector to be injected as the main setpoint
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=206
Type: L2
P052 = 3
P051 = 40
Offline
P645
*
FDS
Source for additional setpoint
Selection of connector to be injected as an additional setpoint
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P646
*
BDS
Source for enable signal for ramp-up integrator switchover
Selection of binector to control enabling of the ramp-function integrator
switchover function.
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
11.33 Control word, status word
Selection of sources of control words 1 and 2
P648
*
BDS
Source for control word 1
Selection of connector to act as the source for control word 1.
0 = connector K0000
...
8 = connector K0008
9 = parameters P654 to P675 are effective
(every individual bit of control word 1 is input by a binector)
10 = connector K0010
etc.
All connector
numbers
1
Ind: 2
FS=9
Type: L2
P052 = 3
P051 = 40
Offline
P649
*
BDS
Source for control word 2
Selection of connector to act as the source for control word 2.
0 = connector K0000
...
8 = connector K0008
9 = parameters P676 to P691 are effective
(every individual bit of control word 2 is input by a binector)
10 = connector K0010
etc.
All connector
numbers
1
Ind: 2
FS=9
Type: L2
P052 = 3
P051 = 40
Offline
Display of control words 1 and 2
r650 Display of control word 1
Mode of representation on operator panel (PMU):
3210
4
5
6
7
89101112131415
Segments 0 to 15 correspond to bits 0 to 15 of the control word
Segment alight: Corresponding bit is in log. "1" state
Segment dark: Corresponding bit is in log. "0" state
Ind: None
Type: V2
P052 = 3