Parameter list 02.00
11-74 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P808
*
Source for activation of F013
Selection of binector which will activate fault message F013 when it
switches to log. "1"
9030 = binector B9030
9031 = binector B9031
9030, 9031 Ind: None
FS=9030
Type: L2
P052 = 3
P051 = 40
Offline
r809 Diagnostic information for G-SST3
Free-running counter, overflow at 65535
i001: Number of error-free telegrams
i002: Number of errored telegrams:
Byte frame, parity, overrun or BCC error
i003: Number of byte frame errors
i004: Number of overrun errors
i005: Parity error
i006: STX error:
Start interval before STX not observed,
telegram residual transfer time not observed,
delay time of LGE character too long,
erroneous STX, i.e. 02
i007: Violation of telegram residual transfer time (USS prot. only)
i008: Block check error
i009: Incorrect telegram length:
With PP802=3 or 4 only:
The length of the received telegram is P801 + P802
(Note: If the received values are correct, they will be processed
even when this error has been detected)
i010: Timeout error:
No valid telegram has been received for a period exceeding the
setting in P807. After the occurrence of a timeout error, this
counter is not activated again until the next valid telegram is
received.
Ind: 10
Type: O2
P052 = 3
r810 Receive data on G-SST1
Display of data received via USS interface 1
i001: Display process data word 1
...
i016 Display process data word 16
i017: Display parameter data word 1
...
i020: Display parameter data word 4
0000 to FFFF H
1
Ind: 20
Type: L2
P052 = 3
r811 Transmit data on G-SST1
Display of data transmitted via USS interface 1
i001: Display process data word 1
...
i016 Display process data word 16
i017: Display parameter data word 1
...
i020: Display parameter data word 4
0000 to FFFF H
1
Ind: 20
Type: L2
P052 = 3