Parameter list 02.00
11-98 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
Tracking/storage elements
The tracking/storage elements are storage elements for the parameterized input quantity. The outputs are linked to connectors.
Transfer of the input quantity is controlled via the RESET, TRACK and STORE functions:
RESET: When the controlling binector reaches log. "1", the output is set to 0.00% (y=0)
TRACK: When the controlling binector reaches log. "1", the output is set to the input value and then tracks it continuously (y=x). If the
TRACK signal switches from "1" to "0", the last value applied to the y output is "frozen"
STORE: With a "0" to "1" transition of the controlling binector signal, the output is permanently set to the current input value (y=x). This
value then remains stored
Priority 1. RESET, 2. TRACK, 3. STORE
Tracking/storage element 1
U222
(2222)
*
S00
Source for input quantity (x) FB 82
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U223
(2223)
*
S00
Source for control signals RESET, TRACK and STORE FB 82
i001: TRACK
i002: STORE
i003: RESET
Settings:
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 3
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U224
(2224)
*
S00
Control word for Power On Mode FB 82
0 Volatile storage:
Zero appears at output when voltage recovers
1 Non-volatile storage:
When the voltage is disconnected or fails, the current output
value is stored and then output when the voltage recovers/is
reconnected
0 to 1
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
Tracking/storage element 2
U225
(2225)
*
S00
Source for input quantity (x) FB 83
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U226
(2226)
*
S00
Source for control signals RESET, TRACK and STORE FB 83
i001: TRACK
i002: STORE
i003: RESET
Settings:
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 3
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U227
(2227)
*
S00
Control word for Power On Mode FB 83
0 Volatile storage:
Zero appears at output when voltage recovers
1 Non-volatile storage:
When the voltage is disconnected or fails, the current output
value is stored and then output when the voltage recovers/is
reconnected
0 to 1
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline