02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-107
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U302
(2302)
S00
Ramp-up time FB 113
0.00 to 300.00
[s]
0.01
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
U303
(2303)
S00
Ramp-down time FB 113
0.00 to 300.00
[s]
0.01
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
11.59 Multiplexer [SW 1.8 and later]
Only active with optional technology software S00
FB86 = 1st multiplexer (output = K9450)
FB87 = 2nd multiplexer (output = K9451)
FB88 = 3rd multiplexer (output = K9452)
Function:
An input quantity is connected through to the output depending on the control bits:
B3 B2 B1 Output y
000 X0
001 X1
010 X2
011 X3
100 X4
101 X5
110 X6
111 X7
U310
(2310)
*
S00
Source for control bits for the multiplexer [SW 1.8 and later]
0 = Binector B0000
1 = Binector B0001
etc.
i001: Control bit B1 for 1st multiplexer
i002: Control bit B2
i003: Control bit B3
i004: Control bit B1 for 2nd multiplexer
i005: Control bit B2
i006: Control bit B3
i007: Control bit B1 for 3rd multiplexer
i008: Control bit B2
i009: Control bit B3
All binector numbers
1
Ind: 9
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
U311
(2311)
*
S00
Source for input quantities for 1st multiplexer [SW 1.8 and later]
0 = Connector K0000
1 = Connector K0001
etc.
i001 Input quantity X0
i002 Input quantity X1
i003 Input quantity X2
i004 Input quantity X3
i005 Input quantity X4
i006 Input quantity X5
i007 Input quantity X6
i008 Input quantity X7
All connector
numbers
1
Ind: 8
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
U312
(2312)
*
S00
Source for input quantities for 2nd multiplexer [SW 1.8 and later]
0 = Connector K0000
1 = Connector K0001
etc.
i001 Input quantity X0
i002 Input quantity X1
i003 Input quantity X2
i004 Input quantity X3
i005 Input quantity X4
i006 Input quantity X5
i007 Input quantity X6
i008 Input quantity X7
All connector
numbers
1
Ind: 8
FS=0
Type: L2
P052 = 3
P051 = 40
off-line