Parameter list 02.00
11-106 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U293
(2293)
S00
Dead zone FB 110
0.00 to 100.00
[%]
0.01
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
Dead zone 3 (output = K9234)
U294
(2294)
*
S00
Source for input quantity FB 111
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U295
(2295)
S00
Dead zone FB 111
0.00 to 100.00
[%]
0.01
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
Setpoint branching (output = K9234)
The input quantity is weighted with 2 parameters:
Parameter U297 determines the output value with an input = 0%
Parameter U298 determines the output value with an input = +100%
-U297 and -U298 apply in the case of negative input values.
The hysteresis set in parameter U299 is applied for transitions from negative to positive input values and vice versa
U296
(2296)
*
S00
Source for input quantity FB 112
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U297
(2297)
S00
Minimum speed FB 112
0.00 to 200.00
[%]
0.01
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
U298
(2298)
S00
Maximum speed FB 112
0.00 to 200.00
[%]
0.01
Ind: None
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online
U299
(2299)
S00
Hysteresis FB 112
0.00 to 100.00
[%]
0.01
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
11.58 Simple ramp-function generator
Parameters apply only if optional S00 technology software is installed
Please note: The output (y) = 0 is set in response to "Set simple ramp-function generator to zero" and POWER ON
The output (y) is frozen at the current value in response to "Stop simple ramp-function generator"
The ramp-up and ramp-down times are set to zero in response to "Bypass simple ramp-function generator"
Ramp-up integrator:
The simple ramp-function generator contains a flip-flop whose output is set to log. "0" (ramp generator initial run) after POWER
ON or when the ramp-function generator has been enabled. When the ramp-function generator output reaches a value
corresponding to the input quantity (y=x) for the first time, the flip-flop output switches to log. "1" and remains in this state until
the next enabling command. This output is linked to binector B9191. By parameterizing U301, index i001=919, it is possible to
apply this binector to the "Bypass simple ramp-function generator" function and thus to implement a ramp-up integrator
function.
U300
(2300)
*
S00
Source for input quantity FB 113
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U301
(2301)
*
S00
Source for control signals FB 113
i001 Source for "Bypass simple ramp-function generator" signal
i002 Source for "Stop simple ramp-function generator" signal
i003 Source for "Reset / enable simple ramp-function generator"
signal
(0 = reset to zero, 1 = enable)
Settings:
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 3
FS=
i001: 0
i002: 0
i003: 1
Type: L2
P052 = 3
P051 = 40
Offline