Parameter list 02.00
11-132 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U746
(2746)
*
SLB Cycle time [SW 1.5 and later]
The cycle time is the period required for all telegrams to be passed around
the SIMOLINK ring. Together with U745, the cycle time determines the
number of addressable nodes.
This parameter is relevant only for the dispatcher.
i001: For first SLB in unit
i002: Reserved
1.00 to 6.50
[ms]
0.01
Ind:2
FS=1.20
Type: O2
P052 = 3
P051 =40
Offline
n748
(2748)
SLB Diagnosis [SW 1.5 and later]
Visualization parameter which displays diagnostic information for an
installed SIMOLINK board (SLB)
i001: Number of error-free synchronizing telegrams
i002: Number of CRC errors
i003: Number of timeout errors
i004: Last accessible bus address
i005: Address of node sending the special telegram "Timeout“
i006: Implemented bus cycle time
i007: Number of new configurations
i008: Reserved
...
i016: Reserved
Ind: 16
Type: O2
P052 = 3
U749
(2749)
*
SLB Read address [SW 1.5 and later]
Definition of node addresses and channels from which the SLB must read
data (a total of 8 channels can be read according to the index entries). The
digits before the decimal point in the input value define the node address
and those after the point the channel number (see also Section 7 "Starting
up SIMOLINK boards" and Section 8 "SIMOLINK board: Receiving,
transmitting").
Example:
2.0 = address 2 channel 1
Changes to the receive data parameters have no effect until the electronics
supply voltage of the drive is switched on again.
0.0 to 200.7
0.1
Ind: 8
FS=0.0
Type: O2
P052 = 3
P051 =40
Offline
n750
(2750)
SLB Receive data [SW 1.5 and later]
Visualization parameter for data received via the SIMOLINK board (see
also Section 7 "Starting up SIMOLINK boards" and Section 8 "SIMOLINK
board: Receiving, transmitting")
i001: Word 1 in PZD section of telegram
...
i016: Word 16 in PZD section of telegram
0000 to FFFF H
1
Ind: 16
Type: L2
P052 = 3
U751
(2751)
*
SLB Transmit data selection [SW 1.5 and later]
Selection of connectors whose contents must be transferred as transmit
data by the SLB (see also Section 7 "Starting up SIMOLINK boards" and
Section 8 "SIMOLINK board: Receiving, transmitting").
0 = connector K0000
1 = connector K0001
etc.
In addition to the transmit data itself, its place in the transmit telegram is
also defined.
i001: Channel0, low word
i002: Channel0, high word
...
i015: Channel7, low word
i016: Channel7, high word
All connector
numbers
Ind: 16
FS=0
Type: L2
P052 = 3
P051 =40
Offline
n752
(2752)
SLB Display of transmit data [SW 1.5 and later]
Process data transmitted by SLB via SIMOLINK in hexadecimal notation
(see also Section 7 "Starting up SIMOLINK boards" and Section 8
"SIMOLINK board: Receiving, transmitting")
Ind: 16
Type: L2
P052 = 3