02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-133
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U753
(2753)
*
SLB Fault delay [SW 1.5 and later]
Delay in activation of fault message F015 (see also U741)
0 = fault message is activated immediately the telegram failure monitor
responds
0.0 to 100.0
[s]
0.1
Ind: None
FS=0.0
Type: O2
P052 = 3
P051 =40
Offline
11.73 Configuring the EB1 expansion board [SW 1.5 and later]
U755
(2755)
*
Signal type of analog inputs on EB1 [SW 1.5 and later]
0 = Voltage input 0 to ± 10 V
1 = Current input 0 to ± 20 mA
i001: AI1 of the first EB1
i002: AI1 of the second EB1
0 to 1
1
Ind: 2
FS=0
Type: O2
P052 = 3
P051 = 40
Online
U756
(2756)
Normalization of analog inputs on EB1 [SW 1.5 and later]
This parameter specifies the percentage value which is generated for an
input voltage of 10V (or an input current of 20mA) at the analog input.
The following general rule applies:
With a voltage input:
UV
Y
X
756 10[%] =∗
X .. input voltage in volts
Y .. % value which is generated for input
voltage X
With a current input:
UmA
Y
X
756 20[%] =∗
X .. input current in mA
Y .. % value which is generated for input
current X
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
-1000.0 to 1000.0
[%]
0.1%
Ind: 6
FS=100.0
Type: I2
P052 = 3
P051 = 40
Online
U757
(2757)
Offset for analog inputs on EB1 [SW 1.5 and later]
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
-100.00 to 100.00
[%]
0.01%
Ind: 6
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
U758
(2758)
*
Mode of signal injection at analog inputs on EB1 [SW 1.5 and later]
0 = Injection of signal with sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
0 to 3
1
Ind: 6
FS=0
Type: O2
P052 = 3
P051 = 40
Offline