Parameter list 02.00
11-140 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U807
(2807)
Telegram failure time on paralleling interface
0 No time monitoring
0.001...65.000 Permissible time interval between two data exchange
operations before a fault message is output.
Fault message F014 is displayed if no data are exchanged with the parallel-
connected converter within this delay period.
The monitoring function is implemented within a 20 ms cycle. For this
reason, only setting values which constitute a multiple of 20 ms are
meaningful.
Note:
The telegram monitoring function is active
• from the receipt of the first error-free telegram after connection of the
electronics power supply
• from the receipt of the first error-free telegram after the telegram
monitor has responded (i.e. monitoring timeout).
0.000 to 65.000
[s]
0.001s
Ind: None
FS=0.100
Type: O2
P052 = 3
P051 = 40
Online
U808
(2808)
*
Source for triggering of message F014
Selection of binector which must trigger message F014 when it switches to
log. "1"
6040 = binector B6040
6041 = binector B6041
6040, 6041 Ind: None
FS=6040
Type: L2
P052 = 3
P051 = 40
Offline
n809
(2809)
Diagnostic information for paralleling interface
i001 to i008=Free-running counter, overflow at 65535
i001: Error-free Telegram Counter
i002: Errored Telegram Counter
i003: Transmit Error Counter
i004: Receive Error Counter
i005: Phase Error Counter
i006: Baud rate Error Counter
i007: Bad BCC Counter
i008: Timeout Counter
i009: Bit 2: Valid telegram received from (if master) / for (if slave)
address 2
...
Bit6: Valid telegram received from (if master) / for (if slave)
address 6
0 to 65535 Ind: 9
Type: O2
P052 ≥ 0
n810
(2810)
Display of active slaves
For master: Display of responding slaves
For slave: Display of slave addresses to which master is sending valid
telegrams
3210456
Ind: None
Type: V2
P052 = 3