02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-141
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
n812
(2812)
Receive data on paralleling interface
When U806=1 (master) is selected
i001 Receive data from slave with address 2, word 1
...
i005 Receive data from slave with address 2, word 5
i006 Receive data from slave with address 3, word 1
...
i010 Receive data from slave with address 3, word 5
i011 Receive data from slave with address 4, word 1
...
i015 Receive data from slave with address 4, word 5
i016 Receive data from slave with address 5, word 1
...
i020 Receive data from slave with address 5, word 5
i021 Receive data from slave with address 6, word 1
...
i025 Receive data from slave with address 6, word 5
When U806=2 to 6 (slave) is selected:
i001 Receive data from master, word 1
...
i005 Receive data from master, word 5
i006 Not in use
...
i025 Not in use
0000 to FFFFH
1
Ind: 25
Type: L2
P052 ≥ 0
n813
(2813)
Transmit data on paralleling interface
When U806=1 (master) is selected
i001 Transmit data to slaves, word 1
...
i005 Transmit data to slaves, word 5
When U806=2 to 6 (slave) is selected:
i001 Transmit data to master, word 1
...
i005 Transmit data to master, word 5
0 to FFFFH Ind: 5
Type: L2
P052 ≥ 0
11.77 Simulation operation
Simulation operation
Simulation operation is used to test the power section (measurement of the firing pulses with a current probe). Firing pulses are output to
a single thyristor (pulse distance = 20 ms, pulse duration = approx. 1 ms, firing pulse chopping as in normal operation). The thyristor is
selected with parameter U840. The line voltage does not have to be applied during simulation operation.
Simulation operation is activated by setting a value > 0 in Parameter U840.
Simulation operation is then actually started when the SIMOREG DC master is in an operating state ≥ o7.
As soon as the SIMOREG DC master is in simulation operation, it goes into operating state o8.1 (simulation operation).
Simulation operation is exited by resetting parameter U840 to zero.
U840
(2840)
*
Control parameters for simulation operation [SW 1.7 and later]
0 No simulation operation
11 Firing cable 11
...
16 Firing cable 16
21 Firing cable 21
...
26 Firing cable 26
0,
11 to 16,
21 to 26
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
off-line
11.78 Parameter for SIMOVIS
n845
to
n949
(2940 to
2949)
These parameters are used by SIMOVIS