02.00 Connections
Siemens AG 6RX1700-0AD76 6-13
SIMOREG DC Master Operating Instructions
6.1.2.3 Arrangement of components for converters
Arrangement of reactors and RI suppression filter
1U1 1V1 1W13U1 3W15U1 5W1
1C1 1D1
M
3C 3D
1)
2)
3)
4)
5N1
NC
400V230V
5U1
5W1
5N1
5)
Line voltage
Field ArmaturePower supply input
either 230V or 400V
SIMOREG-converter
1) The commutating reactor in the field circuit is dimensioned for the rated motor field current.
2) The commutating reactor in the armature circuit is dimensioned for the rated motor current in the
armature. The line current equals DC current x 0.82.
3) The RI suppression filter for the armature circuit is dimensioned for the rated motor current in the
armature. The line current equals DC current x 0.82.
4) The RI suppression filter for the field circuit and the electronics power supply is dimensioned for the rated
motor field current plus 1 A.
5) The RI suppression filter for the electronics power supply is dimensioned for 2 A.
Note:
When RI suppression filters are used, commutating reactors are always required at the converter input to
decouple the snubber circuitry.
Commutating reactors are selected according to information in Catalog DA93.1.