Parameter list 02.00
11-42 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P466
*
FDS
Source for motorized potentiometer setting value
Selection of the connector to be injected as the motorized potentiometer
setting value
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P467
FDS
Motorized potentiometer starting value
Starting value of motorized potentiometer after ON when P473 = 0
-199.9 to 199.9
[%]
0.1%
Ind: 4
FS=0.0
Type: I2
P052 = 3
P051 = 40
Online
P468
FDS
Setpoint for "Raise motorized potentiometer”
Motorized potentiometer manual operation: Setpoint for "Raise motorized
potentiometer"
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=100.00
Type: I2
P052 = 3
P051 = 40
Online
P469
FDS
Setpoint for "Lower motorized potentiometer ”
Motorized potentiometer manual operation: Setpoint for "Lower motorized
potentiometer"
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=-100.00
Type: I2
P052 = 3
P051 = 40
Online
P470
*
BDS
Source for clockwise/counter-clockwise switchover
Selection of binector to control "Clockwise/counter-clockwise
switchover"
("0" state = clockwise).
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P471
*
BDS
Source for manual/automatic switchover
Selection of binector to control "Manual/automatic switchover"
("0" state = manual).
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P472
*
BDS
Source for set motorized potentiometer
Selection of binector to control "Set motorized potentiometer"
("0" to "1" transition = set motorized potentiometer).
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P473
*
FDS
Storage of output value
0 No storage of output value:
The output is set to 0 in all operating states of >o5.
The starting point after ON is determined by P467 (MOP
starting value).
1 Non-volatile storage of output value:
The output value remains stored in all operating states and after
voltage disconnection or failure. The last value stored is output
again after voltage recovery/reconnection.
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline