02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-45
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P494
*
FDS
Motor temperature analog 2 (temperature sensor at terminals 204 /
205): Tripping of alarm or fault message
Motor temperature grasped with KTY84
0 Monitoring deactivated
1 Alarm (A029) at temperature > P491
2 Fault message (F029) at temperature > P492
3 Alarm (A029) at temperature > P491 and
fault message (F029) at temperature > P492
Motor temperature grasped with PTC thermistor
0 Monitoring deactivated
1 Alarm message (A029) when operating point of PTC thermistor
is reached
2 Fault message (F029) when operating point of PTC thermistor
is reached
3 Illegal setting
0 to 3
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P495
*
FDS
Brush length sensing: Tripping of alarm or fault message
0 No brush length sensing (terminal 211 is not scanned)
1 Binary brush length sensing (terminal 211 is scanned)
Alarm (A025) in response to 0 signal
2 Binary brush length sensing (terminal 211 is scanned)
Fault message (F025) in response to 0 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P496
*
FDS
Bearing condition: Tripping of alarm or fault message
0 No bearing condition sensing (terminal 212 is not scanned)
1 Bearing condition sensing (terminal 212 is scanned)
Alarm (A026) in response to 1 signal
2 Bearing condition sensing (terminal 212 is scanned)
Fault message (F026) in response to 1 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P497
*
FDS
Air flow: Tripping of alarm or fault message
0 No air flow monitoring (terminal 213 is not scanned)
1 Air flow monitoring (terminal 213 is scanned)
Alarm (A027) in response to 0 signal
2 Air flow monitoring (terminal 213 is scanned)
Fault message (F027) in response to 0 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P498
*
FDS
Temperature switch: Tripping of alarm or fault message
0 No temperature switch connected (terminal 214 is not scanned)
1 Temperature switch connected (terminal 214 is scanned)
Alarm (A028) in response to 0 signal
2 Temperature switch connected (terminal 214 is scanned)
Fault message (F028) in response to 0 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
11.25 Configuring of torque shell input
P500
*
BDS
Source for torque setpoint for slave drive
Selection of the connector to be injected as the torque setpoint for a
slave drive
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=170
Type: L2
P052 = 3
P051 = 40
Offline
P501
*
BDS
Source for additional torque setpoint
Selection of connector to be injected as the additional torque setpoint
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline