02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-49
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P554
*
FDS
Source for the Influencing quantity of the Tn-adaptation
[SW 1.7 and later]
Selection of which connector is connected at the influencing quantity for
adaptation of the n controllers integration time
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
P555
*
FDS
Source for the Influencing quantity of the droop adaptation
[SW 1.7 and later]
Selection of which connector is connected at the influencing quantity for
adaptation of the n controllers droop
0 = Connector K0000
1 = Connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
P556
FDS
Adaptation n controller P gain: Threshold 1
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
on-line
P557
FDS
Adaptation n controller integration time: Threshold 1 [SW 1.7 and later]
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
on-line
P558
FDS
Adaptation n controller droop: Threshold 1 [SW 1.7 and later]
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
on-line
P559
FDS
Adaptation n controller P gain: Threshold 2
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
on-line
P560
FDS
Adaptation n controller integration time: Threshold 2 [SW 1.7 and later]
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
on-line
P561
FDS
Adaptation n controller droop: Threshold 2 [SW 1.7 and later]
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
on-line
Speed controller - speed droop limitation
P562
FDS
Positive speed droop limitation
0.00 to 199.99
[%]
0.01%
Ind: 4
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online
P563
FDS
Negative speed droop limitation
-199.99 to 0.00
[%]
0.01%
Ind: 4
FS=-100.00
Type: I2
P052 = 3
P051 = 40
Online
11.30 Field reversal
(see also Section 9)
P580
*
BDS
Source for selection of "Direction of rotation reversal using field
reversal”
Selection of binector to control the "Direction of rotation reversal using field
reversal" function
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P581
*
BDS
Source for selection of "Braking with field reversal”
Selection of binector to control the ”Braking with field reversal" function
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline