Parameter list 02.00
11-50 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
11.31 Input quantities for signals
(see also Section 8, Sheet G187 and G188)
P590
*
Source for setpoint of “nset = nact signal”
Setpoint/actual value deviation signal:
Selection of connector to be injected as input quantity "n
set
" for the
setpoint/actual value deviation signal.
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=174
Type: L2
P052 = 3
P051 = 40
Offline
P591
*
Source for actual value of "n-set = n-act signal"
Setpoint/actual value deviation signal:
Selection of connector to be injected as input quantity
"n
act
" for the
setpoint/actual value deviation signal.
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=167
Type: L2
P052 = 3
P051 = 40
Offline
P592
*
Source for actual value of "n < n
comp.
signal”
n < n
comp.
signal:
Selection of connector to be injected as input quantity (n) for the n <
n
comp.
signal.
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=167
Type: L2
P052 = 3
P051 = 40
Offline
P593
*
Source for actual value of “n < n
min
signal”
n < n
min
signal:
Selection of connector to be injected as input quantity (n) for the n < n
min
signal.
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=167
Type: L2
P052 = 3
P051 = 40
Offline
P594
*
Source for input quantity of "Polarity signal”
Polarity signal of speed setpoint:
Selection of connector to be injected as input quantity "n
set
" for the polarity
signal of the speed setpoint.
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=170
Type: L2
P052 = 3
P051 = 40
Offline
P595
*
Source for actual value of "Overspeed signal”
Overspeed signal:
Selection of connector to be injected as input quantity "n
act
" for the
overspeed signal.
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=167
Type: L2
P052 = 3
P051 = 40
Offline
11.32 Configuring of closed-loop control
Setting values for configuring of torque shell
P600
*
Source for gating unit input (armature)
Selection of connector to be injected as the gating unit input (armature)
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=102
Type: L2
P052 = 3
P051 = 40
Offline