02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-51
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P601
*
Source for armature current controller setpoint
i001,i002 Speed limiting controller:
Selection of connectors to be injected as input quantities for
the speed limiting controller. Both values are added.
i003,i004 Current limitation:
Selection of connectors to be injected as armature current
controller setpoint (before current limitation). Both values
are added.
i005,i006 Current control: [SW 1.8 and later]
Selection of which connectors are connected as the armature
current controller setpoint (before current controller). The
two values are added. The magnitude is formed from the
value selected with index 6.
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 6
FS=
i001: 141
i002: 0
i003: 134
i004: 0
i005: 125
i006: 0
Type: L2
P052 = 3
P051 = 40
Offline
P602
*
Source for armature current controller actual value
Selection of connector to be injected as armature current controller
actual value
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=117
Type: L2
P052 = 3
P051 = 40
Offline
P603
*
Source for variable current limit in torque direction I
i001..i004Selection of connector to be injected as variable current limit
in torque direction I
i005 Selection of connector to be injected as current limit in torque
direction I with Fast Stop or Shutdown
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 5
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P604
*
Source for variable current limit in torque direction II
i001..i004Selection of connector to be injected as variable current limit
in torque direction II
i005 Selection of connector to be injected as current limit in torque
direction II with Fast Stop or Shutdown
Settings:
0 = connector K0000
...
8 = connector K0008
9 = value as set in parameter P603.ixx ∗ (−1)
10 = connector K0010
etc.
All connector
numbers
1
Ind: 5
FS=9
Type: L2
P052 = 3
P051 = 40
Offline
P605
*
Source for variable positive torque limit
Torque limitation:
Selection of connectors to be injected as the variable positive torque limit
(100% of connector value corresponds to positive system torque limit
obtained with settings I
a
=P171 and I
f
= P102)
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=2
Type: L2
P052 = 3
P051 = 40
Offline