7.4.3 Safety information
NOTICE
CBE30‑2 damage caused by electric fields or electrostatic discharge
Option boards are ESD-sensitive components.
De-energize the SIMOTION D4x5‑2 device before inserting or removing the option board.
The SIMOTION D4x5‑2 is in a de-energized state when all the LEDs are off.
Observe the ESD guidelines (see Section
ESD guidelines (Page 141)).
7.4.4 Interface description
Characteristics
The
X1400 interface has full-duplex 10/100 Mbit Ethernet ports. The module has an integrated
4-port switch.
Interface characteristics
Table 7-13 X1400 features
Characteristic Type
Connector type RJ45 socket
Cable type Industrial Ethernet cable
Maximum cable length 100 m
Dust protection filler plugs for sealing unused
PROFINET ports
5 filler plugs contained in the D4x5‑2 scope of
delivery
Filler plugs (50 pcs) order number:
6SL3066‑4CA00-0AA0
Interface assignment
Table 7-14
X1400 interface
Representati
on
Pin Name Signal type Description
1 TXP Output Ethernet transmit differential signal
2 TXN Output Ethernet transmit differential signal
3 RXP Input Ethernet receive differential signal
4 -- 4 together with 5 via 75 ohm at the 1 nF
capacitor to the shield ground
5 -- 4 together with 5 via 75 ohm at the 1 nF
capacitor to the shield ground
Supplementary system components
7.4 CBE30-2 Ethernet communication board
SIMOTION D4x5-2