Installation
3.2 Drill pattern SINAMICS G120D
SINAMICS G120D converter
Getting Started, 07/2016, FW V4.7 SP6, A5E38556189B AA
21
Mounting orientation
Mount the converter on a table or on a wall. The minimum clearance distances are as
follows:
Side-by-side - no clearance distance is required
Above and below the inverter 150 mm (5.9 inches).
Image 3-3 Mounting orientation: correct (), impermissible (X), permissible with restrictions (!)
Restrictions due to vertical mounting
If the converter is mounted in the vertical position, the maximum ambient temperature is
40°C.
Additionally you have to reduce the converter output current to 80 % of rated converter
current.
If the output current derating adversely affects the application, you have to use an converter
of the next highest power rating.