Installation
3.14 Connecting the PROFINET interface
SINAMICS G120D converter
Getting Started, 07/2016, FW V4.7 SP6, A5E38556189B AA
59
Setting the PROFIBUS DP address via DIP switches
The PROFIBUS DP address can be set via DIP switch, as shown in the table below.
Table 3- 16 Example address for the PROFIBUS DP interface
DIP switch
1
2
3
4
5
6
7
Add to address
1
2
4
8
16
32
64
Example 1: Address = 3 = 1 + 2
Example 2: Address = 88 = 8 + 16 + 64
3.14
Connecting the PROFINET interface
Industrial Ethernet Cables and cable length
Listed in the table below are the recommended Ethernet cables.
Table 3- 17 Recommended PROFINET cables
Cable type
Max. length be-
tween devices
Article Number
Industrial Ethernet FC TP Standard Cable GP 2 x 2
100 m (328 ft)
6XV1840-2AH10
Industrial Ethernet FC TP Flexible Cable GP 2 x 2
85 m (278 ft)
6XV18702B
Industrial Ethernet FC Trailing Cable GP 2 x 2
85 m (278 ft)
6XV18702D
Industrial Ethernet FC Trailing Cable 2 x 2
85 m (278 ft)
6XV18403AH10
Industrial Ethernet FC Marine Cable 2 x 2
85 m (278 ft)
6XV18404AH10
Cable screening
The screen of the PROFINET cable must be connected with the protective earth. The solid
copper core must not be scored when the insulation is removed from the core ends.