Installation
3.13 Settings PROFIBUS DP address with DIP switches
SINAMICS G120D converter
58 Getting Started, 07/2016, FW V4.7 SP6, A5E38556189B AA
Default setting 27: "EPOS with fieldbus"
DO 0: p0730, DO 1: p0731
3.13
Settings PROFIBUS DP address with DIP switches
Setting the PROFIBUS DP address
Prior to using the PROFIBUS DP interface, the address of the node (Inverter) must be set
using the seven PROFIBUS DP address DIP switches on the Control Unit.
The PROFIBUS DP address can be set between 1 and 126.
Note
The address is taken from P0918 if all PROFIBUS
DP address DIP switches are in the OFF
position, otherwise the DIP switch setting is valid.
NOTICE
External 24 V power supply must be disconnected
The external 24 V power supply must be switched off before the DIP switch settings are
changed. DIP switch setting changes do not take effect until the Control Unit has been
powered-up again.