Installation
3.11 Connections and cables
SINAMICS G120D converter
34 Getting Started, 07/2016, FW V4.7 SP6, A5E38556189B AA
Branch circuit protection according to IEC
Table 3- 6 Branch circuit protection according to IEC
Max. rated current of the protec-
tion device
Article No. of the circuit breaker
3RV2021…, 3RV1031…, 3RV2031…
30 A - 3RV1742
Branch circuit protection according to UL standards
Use in North America requires protection devices that meet UL standards as detailed in the
following tables.
Table 3- 7 Overview of the approved protection devices according to UL standards
Fuses of any manufacturer with faster tripping characteristic than class RK5, e.g.
JDDZ
SIEMENS circuit breaker DIVQ
Intrinsically safe SIEMENS circuit breaker
Table 3- 8 Branch circuit protection with non-semiconductor fuses of Classes J, T, CC, G or CF (UL
Category Code JDDZ)
Max. rated current of the fuse
Short circuit current rating SCCR
Table 3- 9 Branch circuit protection with circuit breaker, UL categories DIVQ and NKJH
Max. rated current of the
circuit breaker
Short circuit current
rating SCCR
30 A
25 A
3RV1031-4DA… or 3RV2031-
NKJH 65 kA, 480Y/277 V AC