EasyManua.ls Logo

Siemens SINAMICS G120D - Commissioning

Siemens SINAMICS G120D
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
3.12 Default settings of inputs and outputs (CU240D-2)
SINAMICS G120D converter
Getting Started, 07/2016, FW V4.7 SP6, A5E38556189B AA
55
Default setting 14: "Process industry with fieldbus"
DO 0: p0730, DO 1: p0731
DI 0: r0722.0, …, DI 5: r0722.5
Motorized potentiometer, setpoint after the ramp-function generator r1050
Speed setpoint (main setpoint): p1070[0] = 2050[1], p1070[1] = 1050

Other manuals for Siemens SINAMICS G120D

Related product manuals