3 Commissioning using IOP-2
G120X commissioning guide for permanent magnet motors PMSM
Entry-ID: 109780815, V1.0, 07/2020
10
© Siemens AG
2020 All rights reserved
3
If you are using any type of output choke
or filter go to Hardware Options and
Output filter and select the right option:
Motor Reactor enter its inductance and
number of reactors connected in series
Dv/dt filter just select this option to
activate filter protection
Sinus Filter Siemens or 3rd party enter
its inductance and capacitance values
from filter nameplate or data sheet. If
Siemens filter is selected the values are
pre-filled already and should equal
nameplate data.
4
In Control Type option select Dynamic
Drive Control
5
Go to Motor Data and enter the
parameters as shown in the table below.
Table 3-2
Motor data
Standard
Depending on power units to be used for commissioning enter
either IEC (50Hz, SI) or NEMA (60Hz, SI) for values in kW or NEMA
(60Hz, US) for values in HP.
Motor Type
2:Sync
Current
Enter Motor Rated Current
Power
Enter Motor Rated Power (mechanical)
Speed
Enter Motor Rated Speed
Voltage
Enter Motor Rated Voltage (refer to NOTE)
Frequency
Enter Motor Rated Frequency