3 Commissioning using IOP-2
G120X commissioning guide for permanent magnet motors PMSM
Entry-ID: 109780815, V1.0, 07/2020
© Siemens AG
2020 All rights reserved
If you are using any type of output choke
or filter go to Hardware Options and
Output filter and select the right option:
Motor Reactor – enter its inductance and
number of reactors connected in series
Dv/dt filter – just select this option to
activate filter protection
Sinus Filter Siemens or 3rd party – enter
its inductance and capacitance values
from filter nameplate or data sheet. If
Siemens filter is selected the values are
pre-filled already and should equal
nameplate data.
In Control Type option select Dynamic
Drive Control
Go to Motor Data and enter the
parameters as shown in the table below.
Depending on power units to be used for commissioning enter
either IEC (50Hz, SI) or NEMA (60Hz, SI) for values in kW or NEMA
(60Hz, US) for values in HP.
Enter Motor Rated Current
Enter Motor Rated Power (mechanical)
Enter Motor Rated Voltage (refer to NOTE)
Enter Motor Rated Frequency