1 Introduction
G120X commissioning guide for permanent magnet motors PMSM
Entry-ID: 109780815, V1.0, 07/2020
3
© Siemens AG
2020 All rights reserved
1 Introduction
1.1 Document purpose
It provides guidance for commissioning permanent magnet synchronous motors (PMSM) with
SINAMICS G120X drives using the IOP-2 interface. Despite the fact the PMSM motors are not
standardized and the optimal performance with G120X drive cannot be always guaranteed most
3
rd
party PMSM motors that meet the criteria described in this guide can be successfully
commissioned.
1.2 Reference list of commissioned PM motors
This document contains information based on several successful tests with PMSM motors.
So far the biggest power rating of the motor that was tested with G120X inverter is
18.5kW/400V. For that reason the information provided in this guide is currently
restricted to applications of up to 18.5kW.
Table 1-1
Make
Type
Design
kW
rpm
V
Hz
Poles
Lq/Ld
Note
Hanning
P3S120-040P0110-
030-003-HS0-029
IPM
1.1
3000
310
150
6
1.3
Lq, Ld set
according to data
sheet
VEM
IE5-PS2R 90 S 4 H
TMP140
SMPM
1.5
3000
310
100
4
1
Lq, Ld set
according to data
sheet
VOLT
Pro
IE5 - 80
IPM
1.5
3000
300
250
10
1.1
ID run ok. Tested
up to 200Hz.
KSB
UMA-S 150E 7/42
Submersible
borehole motor
IPM
4
3000
400
100
4
1.7
Nominal voltage
corrected to
331V. Lq, Ld set
according to data
sheet values.
Tested with sine-
wave filter.
KSB
UMA-S 150E 18/42
Submersible
borehole motor
IPM
18.5
3000
400
100
4
1.6
Nominal voltage
corrected to
366V. Lq, Ld set
according to data
sheet values.
Tested with
du/dt+VPL and
sine-wave filter.