3.1.5 Cable markings
Fundamentals
A visual inspection is made to see whether cables and conductors are marked as defined in the
circuit diagram.
Test procedure
1. The customer selects cables or conductors by random sampling.
Are the cable end tags and conductor colors of cables and conductors marked as defined
in the circuit diagram?
Result
The test is passed if the cable and conductor markings match what is specified in the circuit
diagram.
3.1.6 Setting values of circuit breakers, if used
Fundamentals
The circuit breaker settings are visually checked against what is specified in the circuit diagram.
Test procedure
1. The customer selects circuit breakers by random sampling.
2. The circuit breaker settings are visually checked against what is specified in the circuit
diagram.
Result
The test is passed if the circuit breaker settings match what is specified in the circuit diagram.
3.1.7 Dimensions
Fundamentals
The drive dimensions are measured. The basis for the visual inspection is the order-specific
dimension drawing.
Test procedure
1. The external dimensions, length, width and height of the drive are measured.
Tests
3.1 Visual inspection
SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11