Getting Started
100 A5E37208904-003, 04/2017
p8923[0...
3]
PROFIdrive: Subnet
Sets the subnet mask for the onboard PROFINET interface on the Control Unit.
The active subnet mask is displayed in r8933.
The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
p8925 PROFIdrive: Interface
Setting to activate the interface configuration for the onboard PROFINET interface on the Control
Unit.
p8925 is automatically set to 0 at the end of the operation.
• p8925 = 0: No function
• p8925 = 2: Save and activate configuration
The interface configuration (p8920 and following) is saved and activated after the next POWER ON.
Motor type number is printed on the motor rating plate as motor ID.
For a motor with an incremental encoder, users need to manually input the parameter value.
For a motor with an absolute encoder, the drive automatically reads the parameter value.
p29001 Reversal of motor direc-
Reversal of motor running direction. By default, CW is the positive direction while CCW the nega-
tive direction. After changing of p29001, reference point will lost, A7461 will remind user to referencing again.
• 0: No reversal
•
Selection of BOP operating display.
• 0: Actual speed (default)
• 1: DC voltage
• 2: Actual torque
• 3: Actual position
•
4: Position following error
Selection of control mode.
• 1: Basic positioner control mode (EPOS)
•
2: Speed control mode (S)
p29005
Braking resistor capacity
percentage alarm thresh-
Alarm triggering threshold for the capacity of the internal braking resistor.
Nominal Line supply voltage, effective value of line to line voltage. Drive can operate within -15%
to +10% error.
For 400 V variant servo drive, the value range is 380 V to 480 V, default value is 400 V.
For 200 V variant servo drive, the value range is 200 V to 240 V, default value is 230 V.