Special detectors
Multi
-
sensor fire detector FDOOT241
-
A9
-
Ex
10
008164_y_en_-- 119 | 152
10.6.2 Type Overview
Type Designation Order number Weight [kg]
FDOOT241-A9-Ex Multi-sensor fire detector (Ex) S54329-F7-A1 0.106
Accessories for the multi-sensor fire detector (Ex) FDOOT241-A9-Ex
Type Designation Order number Weight [kg]
DBZ1190-AB Connection terminal BPZ:4942340001 0.001
FDB201 Detector base collective A5Q00003814 0.026
FDB202 Flat, collective detector base S54319-F3-A1 0.025
FDB221 Detector base, addressable A5Q00001664 0.027
FDB222 Flat, addressable detector base S54319-F1-A1 0.026
FDB291 Base attachment A5Q00001603 0.035
FDB295 Base attachment wet S54319-F21-A1 0.286
FDBZ293 Detector locking device A5Q00005035 0.001
FDBZ295 Sealing element S54319-F10-A1 0.062
FDCL221-Ex Line adapter (Ex) S54329-F4-A1 0.240
FDZ291 Detector dust cap A5Q00004814 0.003
- Metal cable gland M20 x 1.5 A5Q00004478 0.036
10.6.3 Technical data
FDOOT241-A9-Ex
Operating current (quiescent) 200…280 µA
Operating temperature -25…+70 °C
Storage temperature -30…+75 °C
Air humidity 95 % rel. (short-term moisture condensation permitted)
Communication protocol FDnet-Ex or collective Ex
Color ~RAL 9010 pure white
Protection category (IEC/EN 60529)
With sealing kit FBZ295
IP43
IP44
Ex classification
IECEx
Directive 2014/34/EU:
(ATEX directive)
Ex ia IIC T4 Ga, Ta = -35…70 °C
II 1 G Ex ia IIC T4 Ga, Ta = -35…70 °C
Standards EN 54-5, EN 54-7