sensor fire detector FDOOT241
10
120 | 152 008164_y_en_--
FDOOT241-A9-Ex
Standards for explosion-hazard areas IEC 60079-0, IEC 60079-11
Ex approvals
● EC-type examination certificate
● IECEx
BVS 12 ATEX E 087 X
IECEx BVS 12.0076 X
Approvals
● VdS
● DNV GL (marine)
G213106
MEDB00003UK
System compatibility
● FDnet
● Collective
FS20 / AlgoRex / SIGMASYS
CS11 / FC10 / XC10 / SIGMASYS
Ex-related connection
data, intrinsically safe
U
i
28 V
I
i
100 mA
P
i
700 mW
L
i
Negligible
C
i
0,2 nF
Line to external alarm
indicator
U
0
14.2 V
I
0
480 mA
P
0
195 mW
L
0
100 µH
C
0
38 nF
Only for connecting passive, external alarm indicators
with negligibly low inductance and capacitance levels.
Symbol Meaning
C
0
Maximum external capacitance
C
i
Maximum internal capacitance
I
0
Maximum output current
I
i
Maximum input current
L
0
Maximum external inductance
L
i
Maximum internal inductance
P
0
Maximum output power
P
i
Maximum input power
U
0
Maximum output voltage
U
i
Maximum input voltage