Special detectors
Manual call point FDM223
-
Ex
10
124 | 152 008164_y_en_--
Ex-related connection
data, intrinsically safe
U
i
28 V
I
i
92 mA
P
i
650 mW
L
i
Negligible
C
i
0,2 nF
Line to external alarm
indicator
U
0
14.2 V
I
0
480 mA
P
0
195 mW
L
0
100 µH
C
0
38 nF
Only for connecting passive, external alarm indicators
with negligibly low inductance and capacitance levels.
Symbol Meaning
C
0
Maximum external capacitance
C
i
Maximum internal capacitance
I
0
Maximum output current
I
i
Maximum input current
L
0
Maximum external inductance
L
i
Maximum internal inductance
P
0
Maximum output power
P
i
Maximum input power
U
0
Maximum output voltage
U
i
Maximum input voltage