2
16 | 152 008164_y_en_--
Multi-sensor fire detector FDOOT241-A
● Point detector with additional heat sensors
● Optional detector dust cap to protect the point detector during the
construction phase
Function
● Functions according to the scattered light principle with two sensors: Optical
forward and backward scattering
● Opto-electronic measuring chamber: Obstructs disruptive extraneous light
but can be relied upon to detect both light and dark smoke particles
● Two additional heat sensors increase the fire detector's immunity to
deceptive phenomena.
● Can be set as a multi-sensor smoke detector, smoke detector, or heat
detector by the software
● Selectable detection behavior thanks to application-specific ASA parameter
sets
Use
● For early detection of flaming fires of solid and liquid substances as well as
of smoldering fires
● For early and reliable fire detection in an environment with deceptive
phenomena
● Can be used addressed
Smoke detector FDO241
● Optional detector dust cap to protect the point detector during the
construction phase
Function
● Functions according to the scattered light principle with one sensor: Optical
forward scattering
● Opto-electronic measuring chamber: Obstructs disruptive extraneous light
but can be relied upon to detect both light and dark smoke particles
● Selectable detection behavior thanks to application-specific ASA parameter
sets
Use
● For early detection of flaming fires as well as smoldering fires
● Can be used addressed