NCK alarms
11/2006 Overview of Alarms
2-21
© Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
1100 No valid firmware
Definitions: No memory card or memory card without valid firmware (license) inserted.
Reaction: Alarm display.
Remedy: Make a note of the error text and contact Siemens AG A&D MC, Hotline (tel./fax: see alarm 1000)
Program
Continuation:
Switch control OFF - ON.
1160 Assertion failed in %1: %2
Parameters: %1 = String (path with program name)
%2 = String (line number)
Definitions: -
Reaction: NC not ready.
The NC switches to follow-up mode.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Alarm reaction delay is canceled.
Remedy: Check the cause of the error in the specified software component at the specified line number.
Program
Continuation:
Clear alarm with the RESET key in all channels. Restart part program.
2000 PLC sign-of-life monitoring
Definitions: The PLC must give a sign of life within a defined period of time (machine data 10100
PLC_CYCLIC_TIMEOUT). If this does not occur, the alarm is triggered.
The sign of life is a counter reading on the internal NC/PLC interface which the PLC causes to count
up with the 10 ms time alarm. The NCK also tests cyclically whether the counter reading has changed.
Reaction: NC not ready.
Local alarm reaction.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department. Check monitoring time frame in NCK-MD
10100 PLC_CYCLIC_TIMEOUT (reference value: 100ms).
Establish the cause of the error in the PLC and eliminate it (analysis of the ISTACK. If monitoring has
responded with a loop in the user program rather than with a PLC Stop, there is no ISTACK entry).
Program
Continuation:
Switch control OFF - ON.
2001 PLC has not started up
Definitions: The PLC must give at least 1 sign of life within a period of time defined in MD 10120
PLC_RUNNINGUP_TIMEOUT (Default setting: 1 sec.).
Reaction: NC not ready.
Local alarm reaction.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: - Please inform the authorized personnel/service department. The monitoring time in in MD 10120
PLC_RUNNINGUP_TIMEOUT must be checked and adapted to the first OB1 cycle.
- Establish the cause of error in the PLC (loop or stop in the user program) and eliminate.
Program
Continuation:
Switch control OFF - ON.