Overview of Alarms 11/2006
HMI alarms
2-674
© Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
113100 Internal error %1
Parameters: %1 = --
Definitions: --
Remedy: --
120000 Area %1 cannot be loaded! Acknowledge alarm, press area switchover
key!
Parameters: %1 = Operating area name
Definitions: One of the applications listed in the REGIE.INI could not be started.
Reaction: Alarm display.
Remedy: Check whether the entry in REGIE.INI is correct.
Program
Continuation:
Internal
120001 Area %1 cannot be selected. Please deactivate area %2
Parameters: %1 = Operating area name
%2 = Operating area name
Definitions: Within the scope of an area switchover, a different area is to be terminated (unloaded).
However, the area refuses this.
The area switchover does not take place.
Reaction: Alarm display.
Remedy: Try again and, if possible, close the reluctant area first.
Program
Continuation:
Internal
120002 Area %1 is still active. Please deactivate area %1
Parameters: %1 = Operating area name
Definitions: When the MMC system is closed (closing the master control), an area is to be terminated.
However, the area refuses this.
The system was NOT closed.
Reaction: Alarm display.
Remedy: Try again and, if possible, close the reluctant area first.
Program
Continuation:
Internal
120003 Area %1 cannot be deactivated. Please try again
Parameters: %1 = Operating area name
Definitions: Within the scope of an area switchover, an area is to be deselected.
However, the area refuses this.
The area switchover does not take place.
Reaction: Alarm display.
Remedy: Try again and, if possible, close the reluctant area first.
Program
Continuation:
Internal
120005 Please acknowledge the dialog box in area %1
Parameters: %1 = Operating area name
Definitions: The area %1 could not be deselected, as in this area a dialog box is still open.
Reaction: Alarm display.
Remedy: Close the dialog box in area %1!
Program
Continuation:
Internal