HMI alarms
11/2006 Overview of Alarms
2-679
© Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
120304 The selection is not possible. The file %1 has insufficient read rights.
Parameters: %1 = Program name with path
Definitions: The file has insufficient read rights for the current access level.
Reaction: Alarm display.
Remedy: Set the required read rights by means of keyswitch or password entry.
The alarm disappears automatically as soon as a program is edited or simulated in the program area.
The alarm can also be acknowledged manually via diagnostics.
Program
Continuation:
Internal
120305 Selection is not possible. The file %1 is currently being edited.
Parameters: %1 = Program name with path
Definitions: The file is currently open in another application (e.g. services) with an editor.
Reaction: Alarm display.
Remedy: Change the program in the already open editor.
The alarm disappears automatically as soon as a program is edited or simulated in the program area.
The alarm can also be acknowledged manually via diagnostics.
Program
Continuation:
Internal
120306 The selection is not possible. The file %1 is selected and active in
channel %2.
Parameters: %1 = Program name with path
%2 = Channel number
Definitions: --
Reaction: Alarm display.
Remedy: Stop the program with the NCU's channel reset and make the selection again.
The alarm disappears automatically as soon as a program is edited or simulated in the program area.
The alarm can also be acknowledged manually via diagnostics.
Program
Continuation:
Internal
120307 The file %1 cannot be opened for the editor because it is selected in
channel %2 for execution from external sources.
Parameters: %1 = Program name with path
%2 = Channel number
Definitions: --
Reaction: Alarm display.
Remedy: A different program on the NCU or for execution from external sources has to be selected.
The alarm disappears automatically as soon as a program is edited or simulated in the program area.
The alarm can also be acknowledged manually via diagnostics.
Program
Continuation:
Internal
120308 In the event of an emergency stop, the program %1 can only be changed
in the machine/program correction area.
Parameters: %1 = Program name with path
Definitions: --
Reaction: Alarm display.
Remedy: Switch to the machine area and change the program with the program correction function.
The alarm disappears automatically as soon as a program is edited or simulated in the program area.
The alarm can also be acknowledged manually via diagnostics.
Program
Continuation:
Internal