Overview of Alarms 11/2006
SIMODRIVE alarms
2-752
© Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
- Modify MD 1216: $MD_CURRENT_FILTER_3_SUPPR_FREQ (suppression frequency current
setpoint filter 3)
- Modify MD 1220: $MD_CURRENT_FILTER_4_BANDWIDTH (bandwidth speed setpoint filter 4) 4)
- Modify MD 1219: $MD_CURRENT_FILTER_4_SUPPR_FREQ (suppression frequency current
setpoint filter 4)
Program
Continuation:
Clear alarm with the RESET key in all channels. Restart part program.
300770 Axis %1 drive %2 format error
Parameters: %1 = NC axis number
%2 = Drive number
Definitions: The calculated filter coefficients of a bandstop filter are beyond the range of the internal format.
The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not
ready).
Reaction: NC not ready.
The NC switches to follow-up mode.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Channel not ready.
Remedy: Please inform the authorized personnel/service department. Change the filter setting. The Hotline
provides support for accurate troubleshooting. Call the SIEMENS AG, SIMODRIVE Hotline.
Program
Continuation:
Clear alarm with the RESET key in all channels. Restart part program.
300771 Axis %1 drive %2 asynchronous mode: converter frequency invalid
Parameters: %1 = NC axis number
%2 = Drive number
Definitions: Only a converter frequency of 4 kHz or 8 kHz is permitted in asynchronous mode (selected by MD
1465 < MD 1146).
- Modify MD 1465: $MD_SWITCH_SPEED_MSD_AM (switchover speed MSD/AM)
- Modify MD 1146: $MD_MOTOR_MAX_ALLOWED_SPEED (maximum motor speed)
The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not
ready).
Reaction: NC not ready.
The NC switches to follow-up mode.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Channel not ready.
Remedy: Please inform the authorized personnel/service department. Modify MD 1100:
$MD_PWM_FREQUENCY (pulse width modulation frequency) or deselect AM mode (make the value
in MD 1465: $MD_SWITCH_SPEED_MSD_AM less than the value in MD 1146:
$MD_MOTOR_MAX_ALLOWED_SPEED.
Program
Continuation:
Clear alarm with the RESET key in all channels. Restart part program.