11/2006 List of Action Numbers
3-853
© Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), Edition 11/2006
No. 126
No. 127
No. 128
No. 129
No. 130
Explanation Implicit change of operating mode to Automatic at the end of a Jog motion in Automatic
mode
See also: $MN_JOG_MODE_MASK
Cause 1. A channel has exited the mode group due to an interrupt.
2. Overstore
Remedy − Abort the program with the Reset key or wait until the interrupt is terminated
− Deselect overstore
Explanation Simulation block search should be initiated, i.e., the calculation results are only dis-
played on the HMI and there is NO traversing even after the block search.
Cause 1. The channel is not in RESET
Remedy − Press Reset key
Explanation Refusal to execute program area
Cause 1. The channel is not in RESET
2. The channel is not in Automatic mode
Remedy − Press Reset key
− Switch to Automatic mode
Explanation Refusal to select PI service syntax check "_N_CHKSEL"
Cause The channel is not in RESET
Remedy Press Reset key
Explanation Refusal to start PI service syntax check "_N_CHKRUN"
Cause The channel is not in RESET
Remedy Press Reset key