Preparing for Operation
60
SIP ART PS2 Manual
A5E00074631-01
5. Start initialization by pressing the key for longer than 5 s.
Display:
During the initialization phase RUN1”to”RUN5 appear one after an-
other in the bottom display (see also structograms figures 3-24,
page 68 to figure 3-27, page 71).
.
NOTE
The initialization process may last up to 15 minutes depending on the
actuator .
The initialization is complete when the following display appears:
The following display appears after pressing the operation mode key
briefly:
To exit the Configuration operating mode, press the
operation mode key
for longer than 5 s. The software version is dis-
played after about 5 s. The instrument is in manual operation after re-
leasing the operation mode key.
.
NOTE
You can abort an ongoing initialization at any time by pressing the
operation mode key. Your previous settings are retained. All the para-
meters are reset to the factory setting only after performing a “Preset”.