EasyManua.ls Logo

Siemens SIPART PS2 series - Page 14

Siemens SIPART PS2 series
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electropneumatic positioners
SIPART PS2
Technical specifications
SIPART PS2 FF
6/14
Siemens FI 01 · 2009
6
Communication
Communications group and class According to technical specification of the Fieldbus Foundation for H1 communication
Function blocks Group 3, Class 31PS (publisher, subscriber)
1 resource block (RB2)
1 analog output function block (AO)
1 PID function block (PID)
1 transducer block (standard advanced positioner valve)
Execution times of the blocks AO: 50 ms
PID: 80 ms
Physical layer profile 123, 511
FF registration Tested with ITK 5.0
Device address 22 (when delivered)
Connections
Electric Screw terminals 2.5
AWG28-12
Cable gland M20 x 1.5 or
½-14 NPT
Screw terminals 2.5
AWG28-12
EEx d certified cable
gland M20 x 1.5,
½-14 NPT or M25 x 1.5
Screw terminals 2.5
AWG28-12
Cable gland M20 x 1.5 or
½-14 NPT
Screw terminals 2.5
AWG28-12
Cable gland M20 x 1.5 or
½-14 NPT
Pneumatic Female thread G¼ DIN
EN ISO 228-1 (¼-18 NPT)
Female thread G¼ DIN
EN ISO 228-1 (¼-18 NPT)
Female thread G¼ DIN
EN ISO 228-1 (¼-18 NPT)
Female thread G¼ DIN
EN ISO 228-1 (¼-18 NPT)
External position sensor
(potentiometer or NCS; as option)
•U
o
––< 5V<5V
•I
o
––<75mA<75mA
•I
s
––<160mA<160mA
•P
o
< 120 mW < 120 mW
Maximum permissible external capaci-
tance C
o
––< 1 μF< 1 μF
Maximum permissible external induc-
tance L
o
< 1 mH < 1 mH
SIPART PS2 FF Basic device
without Ex protection
Basic device
with Ex d protection
(flameproof casing)
Basic device
with Ex ia/ib protection
Basic device
with Ex n/dust protec-
tion
© Siemens AG 2008

Other manuals for Siemens SIPART PS2 series

Related product manuals