EasyManua.ls Logo

Siemens SIPART PS2 series - Page 8

Siemens SIPART PS2 series
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electropneumatic positioners
SIPART PS2
Technical specifications
all versions
6/8
Siemens FI 01 · 2009
6
Technical specifications
SIPART PS2 (all versions)
General data
Travel range (linear actuators) 3 ... 130 mm (0.12 ... 5.12 inch)
(angle of feedback shaft 16 ... 90°)
Angle of rotation
(part-turn actuators)
30 ... 100°
Installation
On linear actuators Using attachment set
6DR4004-8V and where necessary
with an additional lever arm
6DR4004-8L on actuators accord-
ing to IEC 534-6 (NAMUR) with
ribs, bars or flat face
On part-turn actuators Using attachment set
6DR4004-8D on actuators with
mounting plane according to
VDI/VDE 3845 and DIN 3337:
The required mounting console
has to be provided on the actuator
side; shaft with groove and female
thread M6
Controller
Five-point switch Self-adjusting
Dead zone
- dEbA = Auto Self-adjusting or can be set as
fixed value
- dEbA = 0.1 ... 10% Self-adjusting or can be set as
fixed value
A/D converter
Scan time 10 ms
Resolution 0.05%
Transmission error 0.2%
Temperature effect 0.1%/10 K ( 0.1%/18 °F)
Cycle time
20 mA/HART device 20 ms
PA device 60 ms
FF device 60 ms (min. loop time)
Binary input BE1 (terminals 9/10;
electrically connected to the basic
device)
Suitable only for floating contact;
max. contact load < 5 mA with 3 V
Degree of protection IP66 to EN 60 529/NEMA 4x
CE marking Conformity as regards EMC Direc-
tive 89/336 EC in accordance with
the following standards
EMC requirements EN 61326/A1 Appendix A.1 and
NAMUR NE21 August 98
Material
Housing
- 6DR5..0-... (plastic) Glass-fiber-reinforced Macrolon
- 6DR5..1-... (metal) GD AISi12
- 6DR5..2-... (stainless steel) Austenitic stainless steel mat.
No. 1.4581
- 6DR5..5-... (metal, pressure-
proof)
GK AISi12
Pressure gauge block Aluminium AIMgSi, anodized
Vibration resistance
Harmonic oscillations
(sine-wave) according to
DIN EN 60062-2-6/05.96
3.5 mm (0.14 inch), 2 ... 27 Hz
3 cycles/axis
98.1 m/s² (321.84 ft/s²),
27 ... 300 Hz, 3 cycles/axis
Bumping (half-sine)
to DIN EN 60068-2-29/03.95
150 m/s² (492 ft/s²), 6 ms,
1000 shocks/axis
Noise (digitally controlled)
to DIN EN 60068-2-64/08.95
10 ... 200 Hz; 1 (m/s²)²/Hz
(3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz
(0.98 (ft/s²)²/Hz)
4 hours/axis
Recommended continuous duty
range of the complete fitting
30 m/s² ( 98.4 ft/s²) without res-
onance sharpness
Weight, basic device
Plastic casing Approx. 0.9 kg (1.98 lb)
Metal casing, aluminium Approx. 1.3 kg (2.86 lb)
Metal casing, stainless steel Approx. 3.9 kg (8.58 lb)
Metal casing EEx d version Approx. 5.2 kg (11.46 lb)
Dimensions See "Dimensional drawings"
Climate class 4 To DIN EN 60721-3-4
Storage
1)
1K5, but -40 ... +80 °C
(1K5, but -40 ... +176 °F)
•Transport
1)
2K4, but -40 ... +80 °C
(2K4, but -40 ... +176 °F)
Operation
2)
4K3, but -30 ... +80 °C
3)
(4K3, but -22 ... +176 °F)
Certificate and approvals
Classification according to pres-
sure equipment
directive (DRGL 97/23/EC)
For gases of fluid group 1, com-
plies with requirements of article 3,
paragraph 3 (sound engineering
practice SEP)
Pneumatic data
Power supply Compressed air, nitrogen or
cleaned natural gas
Pressure 1.4 ... 7 bar (20.3 ... 101.5 psi):
Sufficiently greater than max. drive
pressure (actuating pressure)
Air quality to ISO 8573-1
Solid particle size and density Class 2
Pressure dew point Class 2 (min. 20 K (36 °F) below
ambient temperature)
Oil content Class 2
Unthrottled flow
Inlet air valve
(ventilate actuator)
4)
- 2 bar (29 psi) 4.1 Nm³/h (18.1 USgpm)
- 4 bar (58 psi) 7.1 Nm³/h (31.3 USgpm)
- 6 bar (87 psi) 9.8 Nm³/h (43.1 USgpm)
Outlet air valve
(exhaust actuator)
4)
- 2 bar (29 psi) 8.2 Nm³/h (36.1 USgpm)
- 4 bar (58 psi) 13.7 Nm³/h (60.3 USgpm)
- 6 bar (87 psi) 19.2 Nm³/h (84.5 USgpm)
Valve leakage < 610
-4
Nm³/h (0.0026 USgpm)
Throttle ratio Adjustable up to : 1
Power consumption in the
controlled state
< 3.610
-2
Nm³/h (0.158 USgpm)
Types of actuators
In casing Single-action and double-action
In aluminium casing Single-action
In flameproof casing Single-action and double-action
In stainless steel casing Single-action and double-action
1)
During commissioning at 0 °C ( 32 °F) make sure that the valves are
flushed long enough with the dry medium.
2)
At -10 °C (14 °F) the display refresh rate of the LCD is limited. Only T4 is
permissible when using I
y
module.
3)
-25 ... +75 °C (-13 ... +167 °F) for 6DR55..-0G..., 6DR56..-0G...,
6DR55..-0D... and 6DR56..-0D...
4)
With EEx d version (6DR5..5-...) the values are reduced by approx. 20%.
© Siemens AG 2008