f < 10 Hz
f > 80 Hz
Active
Tolerances
Currents 1 % of the setting value or 5 mA (I
rated
= 1 A)
or 25 mA (I
rated
= 5 A), (f
rated
± 10 %)
Voltages 0.5 % of the setting value or 0.5 V
Time delays 1 % of the setting value or 10 ms
Technical Data
11.46 Measuring-Voltage Failure Detection
SIPROTEC 5, High-Voltage Bay Controller, Manual 1215
C53000-G5040-C015-A, Edition 05.2018