Filtration 
   
 
 
© Siemens AG, 2004. All rights reserved 
EMC Installation Guideline – Planning Guide (EMV) – 03.2004 Edition 
7-47 
Wiring 
·  Supply lines and shunts to the filter are to be routed with spatial separation. 
·  Power and signal lines must basically be conducted separately. For this, the 
power lines from the converter must be conducted functionally downwards and 
the transmitter lines upwards, to achieve as large a spatial distance as possible 
(see also Chapter 6 for this). 
·  To comply with the radio interference thresholds, it is necessary to create all 
motors and main lines with shielding. Optionally, an earthed metal channel with 
an electrically extensive contacted cover may be used. The extensive link of the 
shielding to the appropriate components (motor, converter) must always be 
ensured. 
 
Functional earthing 
The extensive conducting assembly of the filter in the cabinet provides the 
functional earthing. If only a more or less insulated installation is possible, then the 
functional earthing must be provided via an equipotential bonding conductor. 
 
Protection earthing 
Basically, the regulations for protection earthing also apply. However, additional 
measures are necessary for converters due to the high deflection currents. 
 
 
Caution 
According to EN 50178, only currents ≤ AC 3.5 mA or ≤ DC 10 mA may flow to a 
conductor. As the interference currents of current converter-filters normally 
exceed these values, the following measures must be performed: 
1.  Laying of a second conductor via separated clamps parallel to the current 
conductor, whereby this equipotential bonding conductor must likewise meet 
the requirements for conductors according to IEC 364-6-543. 
2.  Use of a conductor with a cross-section ≥ 10mm
2
 Cu. 
 
 
! 
 
Warning 
Unused cores of power lines (e.g. brake cores) and their line shields must be 
installed on at least one side to the earthing potential in order to discharge the 
loads arising through capacitive overcoupling. Hazardous contact voltages on the 
unearthed shields and cores may arise if this warning is disregarded. 
 
n