Siemens SITRANS LVL200E - Step-by-Step Connection Procedure; Wiring Plan: Single Chamber Housing

Siemens SITRANS LVL200E
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
We recommend connecting SITRANS LVL200E in such a way that the
switching circuit is open when there is a level signal, line break or
failure (safe condition).
Information:
The contactless electronic switch is always shown in non-operative
condition.
Warning:
The instrument must not be operated without an intermediately
connected load, because the electronics would be destroyed if
connected directly to the mains. It is not suitable for connection to low
voltage PLC inputs.
For direct control of relays, contactors, magnet valves, warning lights,
horns etc.
Domestic current is temporarily lowered below 1 mA after switching o
the load so that contactors, whose holding current is lower than the
constant domestic current of the electronics, are reliably switched o.
When SITRANS LVL200E is used as part of an overll protection
system according to WHG, also note the regulations of the general
type approval.
1
2
AC
DC
L1
+
-
N
-
+
Fig. 11: Wiring plan, single chamber housing
Wiring plan
SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH 19
5 Connecting to power supply
33839-EN-100908