EasyManua.ls Logo

Siemens SMART 7KT - Connection Diagrams for SMART 7 KT; Circuit Diagram - 3 Phase 4-Wire System

Siemens SMART 7KT
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
MODBUS REGISTER ADDRESSES LIST (Continued)
Readable / writable parameters: [Data Structure: Integer]
Address
Hex
Address
Parameter Range
Length
(Register)
40000 0x00 Password Min value: 0 Max value: 9998 1
40001 0x01 N/W Selection Value: 0 Meaning: 3P4W 1
Value: 1 Meaning: 3P3W 1
Value: 2 Meaning: 1P2W-P1 1
Value: 3 Meaning: 1P2W-P2 1
Value: 4 Meaning: 1P2W-P3 1
40002 0x02 CT Secondary Min value: 1 Max value: 5 1
40003 0x03 CT primary (CT Secondary=5)(A) Min value: 5 Max value: 10000 1
CT primary (CT Secondary=1)(A) Min value: 1 Max value: 10000
40004 0x04 PT Secondary Min value: 100 Max value: 500 1
40006 0x06 PT primary Min value: 100 Max value: 500kV 2
40007 0x07 Slave id Min value: 1 Max value: 255 1
40008 0x08 Baud rate Value: 0x0000 Meaning: 300 1
Value: 0x0001 Meaning: 600
Value: 0x0002 Meaning: 1200
Value: 0x0003 Meaning: 2400
Value: 0x0004 Meaning: 4800
Value: 0x0005 Meaning: 9600
Value: 0x0006 Meaning: 19200
40009 0x09 Parity Value: 0x0000 Meaning: None 1
Value: 0x0001 Meaning: Odd
Value: 0x0002 Meaning: Even
40010 0x0A Stop bit Value: 0x0000 Meaning: 1 1
Value: 0x0001 Meaning: 2 1
40011 0x0B Backlight OFF Min Value: 0 Max Value: 7200 1
40012 0x0C Factory Default Value: 1 Meaning: Set to factory setting range 1
40016 0x10 Auto Mode Pages Min Value: 1 Max Value: 22
Page No Meaning
40017 0x11 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40018 0x12 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40019 0x13 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40020 0x14 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40021 0x15 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40022 0x16 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40023 0x17 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40024 0x18 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40025 0x19 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40026 0x1A Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40027 0x1B Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40028 0x1C Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40029 0x1D Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40030 0x1E Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40031 0x1F Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40032 0x20 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40033 0x21 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40054 0x36 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40055 0x37 Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40059 0x3B Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40060 0x3C Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40061 0x3D Page Address Sequence 1-22 1-First Page; 22-Last Page 1
40034 0x22 Demand Interval Method Value: 0x0000 Meaning: Sliding 1
Value: 0x0001 Meaning: Fixed 1
40035 0x23 Demand Interval Duration MIN Value: 1 MAX Value: 30 1
40036 0x24 Demand Interval Length MIN Value: 1 MAX Value: 30 1
40043 0x2B Reset Max Value: 1 Meaning: Reset all Max power 1
40044 0x2C Reset Energy Value: 1 Meaning: Reset all energyto factory setting range 1
40046 0x2E Reset ON Hour Value: 1 Meaning: Reset ON hour 1
9
Circuit Diagram
3 Phase 4-Wire (commonly used)
3 Ø - 4 Wire, 3 CT’S
3 Ø - 4 Wire, 3 CT’S and 3 PT’S
Connection diagram for communication
RS485-RS232
Converter
Master
Suggested
terminating resistor
(120 ohm,¼watt)
F2
F3 F4
F1
F2
F3 F4
F1
F2
F3 F4
F1
Contact sales for PC based monitoring software to communicate
with the meters.
S2S1 S2S1 S2S1 NV2V3
LOADLINE
L1
L2
L3
N
I1
I2
I3
V1
2)
DI RS485
L
N
LN
#
++
+
SMART7KT
Voltageupto 500V without PT
LINE
DI RS485
L
N
LN
#
LOAD
L1
L2
L3
N
2)
S2S1 S2S1 S2S1 NV1V2V3
I1
I2
I3
++
+
SMART7KT
Voltage 100V-500kV withPT
2) All Fuse Type: 0.5A, Class gG