34
SMART 7KT0311 Manual
Modbus register addresses list (Continued)
Address
Hex
Address
Parameter Range
Length
(Register)
40033 0x21 Pagesequence17 1 to 23 1:FirstPage:23:Lastpage 1
40054 0x36 Pagesequence18 1 to 23 1:FirstPage:23:Lastpage 1
40055 0x37 Pagesequence19 1 to 23 1:FirstPage:23:Lastpage 1
40059 0x3B Pagesequence20 1 to 23 1:FirstPage:23:Lastpage 1
40060 0x3C Pagesequence21 1 to 23 1:FirstPage:23:Lastpage 1
40061 0x3D Pagesequence22 1 to 23 1:FirstPage:23:Lastpage 1
40062 0x3E Pagesequence23 1 to 23 1:FirstPage:23:Lastpage 1
40034 0x22 DemandIntervalMethod MinValue:0x0000 Meaning:Sliding 1
MinValue:0x0001 Meaning:Fixed 1
40035 0x23 DemandIntervalduration MinValue:1 MaxValue:30 1
40036 0x24 DemandIntervallength MinValue:1 MaxValue:30 1
40057 0x39 PulseDuration(Sec) MinValue:1 MaxValue:20 1
40058 0x3A PulseWeight(kWh) MinValue:1 MaxValue:9999 1
40043 0x2B ResetMAXcurrentandpower MinValue:1 Meaning:ResetallMAXPowerand
Current
1
40044 0x2C ResetEnergymains MinValue:1 Meaning:Resetallmainsenergyto
factorysettingrange
1
40046 0x2E Reset ON hour MinValue:1 Meaning:ResetONHour 1
40047 0x2F ResetEnergyDI MinValue:1 Meaning:ResetallDienergytofactory
settingrange
1